By Mike Sokol
If you recall the survey we did July, 2010 in RVtravel.com, you know that 21 percent of RVers who answered the survey have been shocked by their RV. Review the 21 percent report at www.noshockzone.org/15. What follows is the eighth segment of a 12-part series about basic electricity for RV users and how to protect yourself and your family from shocks and possible electrocution.
This series of articles is provided as a helpful educational assist in your RV travels, and is not intended to have you circumvent an electrician. The author and the HOW-TO Sound Workshops will not be held liable or responsible for any injury resulting from reader error or misuse of the information contained in these articles. If you feel you have a dangerous electrical condition in your RV or at a campground, make sure to contact a qualified, licensed electrician.
GFCI review
If you don’t already know what a GFCI circuit breaker is, please read part VIII on basic theory and operation of this lifesaving device. GFCI devices are among the least understood of all electrical safety circuits, but their function is really pretty simple once you understand their basic operating principals.
It’s All About Balance
Here’s the illustration we used in Part XIII to demonstrate what a GFCI is looking for electrically. Note that a perfectly isolated electrical appliance should have exactly the same amount of electrical current going out and coming back in. For example, if an applicance draws 7.000 amperes of current from the black/hot wire, then exactly 7.000 amperes of return current should be coming back in the white wire. However, if there’s any secondary connection to the earth/ground from something like our happy camper poking a piece of metal in a socket while standing on the ground, there will now be more current going out the black wire than is returning from the white wire.
GFCI breakers in America are designed to trip when there’s any more than 5 milliamperes of difference between the black and white wires. Note that a GFCI breaker doesn’t really need the green/ground wire at all to function. The GFCI detector circuit only cares about what’s going out of the black wire compared to what’s coming back into the white wire.
Nuisance Tripping
What bothers many campers and home owners about GFCI breakers is that they’ll occasionally trip for no apparent reason. So if you plug your shore power to the GFCI outlet in your garage to run your RV refrigerator while you’re stocking for an extended trip next week, you may come back the following day to find the power out and your food spoiled. Nobody was in the RV and nothing looks out of place. Or you plug in a power drill to your exterior RV outlet and BAM! it trips before you can pull the trigger on the drill. Why would that happen when the drill runs just fine in your basement workshop? Those sorts of situations are what makes home and RV owners suspicious of GFCIs and want to replace them with a non-protected outlet — which, I might add, is illegal to do.
Less Than Perfect?
What could cause an appliance or electrical circuit to behave badly and fool a GFCI into tripping? Glad you asked. Every appliance has at least two separate wires connecting it to the power outlet, and many will have a third “green” wire known as the safety ground. The purpose of this ground wire is to drain off any electrical leakage within the appliance itself that might occur from deteriorated insulation, a pinched wire or perhaps a failed component such as a power transformer or light bulb socket with water inside.
This deterioration or component failure often occurs in old electrical appliances. So if you’re plugging in a Fender guitar amp from your teenage years, the amp probably has a lot of heat damage to the power transformer from those extended bar jams of “Smoke on the Water.” That overheating is what causes that peculiar “burnt transformer” smell that we also associate with a bad fluorescent light ballast.
An appliance’s or amplifier’s insulation breakdown doesn’t always result in a complete short circuit that would trip a regular 20-amp circuit breaker. It can be like a small leak in a pipe that’s dripping water just a bit. So let’s assume that there’s 10 milliamperes of electrical leakage from the hot/black wire of the power cord to the chassis of your amplifier. That’s way less than the 3 or 4 amperes of current your amp is drawing from the circuit to run the tubes and power the speakers. Therefore, a 20-amp circuit breaker thinks that all is well.
However, plug that same guitar amplifier into a GFCI breaker and it sees there are 4.010 amperes of current going to the black wire and only 4.000 amperes of current coming back from the white wire. Where did those extra 10 milliamperes (0.010 amps) of current go? Well, back through the green wire that ties to the white wire way back at the electrical panel. But since the GFCI doesn’t know or care if that extra 10 mA of current was properly disposed of via the green ground wire or your hand touching the electrified chassis of the amplifier, it trips the breaker in an attempt to save your life. Let’s not call this nuisance tripping, but rather life-saving tripping.
Charting Fault Combinations
So here are two ways to determine which of your appliances is tripping the GFCI. The first is pretty simple. Just unplug every appliance from its own electrical outlet and begin plugging them back in one at a time and turning them on. You’ll want to cycle the appliance on and off a few times since there can be ground fault current “spikes” when you turn on a microwave or light switch. But here’s where it gets tricky: ground fault currents are additive. So if you have two appliances that are each leaking 4 mA (milliamperes) of current to ground, turning on either one of them won’t trip your GFCI, but turning on both appliances at the same time will allow their fault currents of 4 mA and 4 mA to add up to 8 mA. And, of course, 8 mA is greater than the 5 mA limit of the GFCI breaker so it trips.
This might require a little detective work, but I usually make a simple chart or spreadsheet of all my appliances and turn them on singly and in combination with every other possible appliance. Charting seems like an unnecessary step, but that’s when you’ll see obvious combinations that cause a problem, like in my chart above. It shows that when I turned on both the porch light and the microwave, the GFCI would trip. Now I know there’s something electrically leaking to ground in both the porch light and microwave. The porch light might have a water leak in the wall, which is letting moisture into an unsealed electrical box, while the microwave could have a chaffed wire from bouncing down the highway for the last few years. Both problems should be corrected since they’ll only get worse, not better, with age.
Measure It
There is, however, an even better method if you’re an RV tech or can borrow or buy a clamp-on ammeter such as the Fluke shown in the picture. To do this properly you’ll need a meter that can display down to 0.001 amperes, which is 1 mA resolution. Clamp-on ammeters have a current transformer that looks for current flowing through the wires placed inside their jaws. However, if you simply clamp them around the entire power cord of an appliance, you’ll be summing the current going out from the black wire with the currents returning from the green and white wires and you won’t know the actual ground leakage current. Because the GFCI ignores the green wire current in its own leakage calculations, we need to do the same thing with our clamp-on ammeter to get the real currents involved.
You can do this ground fault leakage test by sacrificing a short extension cord to make a test cable. (Don’t you feel like a scientist, now?). With the extension cord unplugged from everything, just slit off the outer covering, being careful not to nick the insulation of the black, white or green wires.
This allows you to plug your appliances one at a time into a non-GFCI outlet using your test cable to see how much current is leaking back to ground. Clamp the ammeter around the black (hot) and white (neutral) wires as shown in the picture, keeping the green (ground) wire out of the jaws. Your ammeter will now be registering how much current is going out the black wire minus how much is coming back the white wire. So any currents you read on the meter will be the ground leakage that can cause the GFCI to trip from that appliance.
Note that there’s going to be a certain amount of leakage to ground from anything plugged into a wall outlet. So 1 mA or so is not a problem. In this case I have 0.0008 amps which is 0.8 mA of current flow, just less than 1 mA. That by itself shouldn’t cause a GFCI to trip. But you can see that if you have five appliances plugged into a single GFCI (like a campsite 20-amp receptacle) and each one is leaking around 1 mA of current to ground, then that GFCI breaker is going to trip whenever it feels like doing so.
Troubleshooting each appliance for ground fault leakage is beyond the scope of this article, but once you’ve identified the problem, you can either replace or repair each item, checking again with your clamp-on ammeter to confirm you’ve fixed the current leak to ground. Once your total ground leakage current is below 5 mA, then your random GFCI tripping should become a thing of the past.
Wrap Up
GFCI breakers always trip for a reason, and that reason is they see an imbalance between how much current is going out to an appliance from the black wire compared to how much is coming back in from the white wire. If you clamp an ammeter around the black and white wires at the same time, any current flow detected will be ground leakage within the appliance itself. Over 5 mA of leakage to ground is supposed to trip a residential GFCI, so it’s only doing its job.
Future Shock
Part XI of this series will cover extension cord connector wiring and testing, so come back next week. See you then.
Feedback
After you’ve read this article at RVtravel.com, take a trip over to www.NoShockZone.org and send us your comments and suggestions. We love to know how we’re doing with this important project.
****
Read all the segments in this series.
Mike Sokol is the chief instructor for the HOW-TO Sound Workshops (www.howtosound.com) and the HOW-TO Church Sound Workshops. He is also an electrical and professional sound expert with 40 years in the industry. Visit www.NoShockZone.org for more electrical safety tips for both RVers and musicians. Contact him at mike@noshockzone.org.